Product Spectrum

HP Pro Series 1 KVA to 10 KVA Online UPS

HP Series is a True Online double conversion UPS with high frequency transformer less design available in 1KVA to 10KVA capacity. It is fully Microprocessor control system with wide input voltage range. This UPS employs the Advance PFC technology with intelligent Battery Management System.

Features

  • True double-conversion
  • Microprocessor control optimizes reliability
  • Wide input voltage range
  • Advance battery management
  • Self testing when UPS start up
  • Network/Fax/Modem Surge Protection
  • EMI/RFI noise filter
  • Charger for longer backup
  • Inbuilt batteries option
  • Converter mode available
  • ECO mode for energy saving (Only available for 1-3KVA)
  • Generator compatible
  • Smart SNMP works well with either USB or RS-232 together
  • Comprehensive display allows easy monitoring and access of UPS status
  • Optional isolation transformer offers full isolation and complete common mode noise rejection

Specification

MODEL HP PRO 1101 HP PRO 1102 HP PRO 1103 HP PRO 1106 HP PRO 1110
CAPACITY 1000 VA / 800 W 2000 VA / 1600 W 3000 VA / 2400 W 6000 VA / 4800 W 10000 VA / 8000 W
INPUT
Nominal Voltage 100/110/115/120/127VAC or 200/208/220/230/240VAC 208/220/230/240VAC
Input Voltage Range 55-150 VAC or 110-300 VAC at 50% load 110-300 VAC at 50% load
85-140 VAC or 160-280 VAC at 100% load 176-300 VAC at 100% load
Frequency Range 40 Hz ~ 70 Hz 46~54 Hz or 56~64 Hz
Power Factor ≧0.99 @ Nominall Voltage (100% load)
OUTPUT
Output Voltage 100/110/115/120/127VAC or 200/208/220/230/240VAC 208/220/230/240VAC
Voltage Requlation ± 1 %
Frequency Range (Synchronized Range) 47~ 53 Hz or 57 ~ 63 Hz 46~54 Hz or 56~64 Hz
Frequency Range (Batt. Mode) 50 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio 3:01
Harmonic Distortion ≦ 3 % THD (Linear Load) ≦ 3 % THD (Linear Load)
≦ 6 % THD (Non-linear Load) ≦ 5 % THD (Non-linear Load)
Transfer Time AC to DC Zero
Inverter to Bypass 4 ms (Typical) Zero
Waveform (Batt. Mode) Pure Sinewave
EFFICIENCY
To AC Mode 88% 88% 90% 92% 93%
To Battery Mode 83% 85% 88% 90% 91%
BATTERY
Standard Model Battery Type 12 V / 9 Ah 12 V / 9 Ah 12 V / 9 Ah 12 V / 9 Ah
Numbers 2 4 6 16
Typical Recharge Time 4 hours recover to 90% capacity 9 hours recover to 90% capacity
Charging Current (Max.) 1.0 A 1A, 2A, 4A, 6A (Adjustable)
Charging Voltage 27.4VDC ± 1% 54.7 VDC ±1% 82.1 VDC ±1% 218.4 VDC ±1%
Long-run Model Battery Type and Numbers Depending on the capacity of external batteries
Charging Current (Max.) 1A-6A (Adjustable) 1A, 2A, 4A, 6A (Adjustable)
Charging Voltage 27.4VDC 41.0VDC ± 1% 54.7 VDC 82.1 VDC 109.4VDC 82.1 VDC 109.4VDC 218.4 VDC ±1%
± 1% ±1% ±1% ±1% ±1% ±1%
INDICATORS
LCD Display Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators
ALARM
Battery Mode Sounding every 4 seconds
Low Battery Sounding every second
Overload Sounding twice every second
Fault Continously sounding
PHYSICAL
Standard Model Dimension, DxWxH (mm) 282 x 145 x 220 397 x 145 x 220 421 x 190 x 318 369 x 190 x 688 442 x 190 x 688
Net Weight (kgs) 9.8 17 27.6 63 66
Long-run Model Dimension, DxWxH (mm) 282 x 145 x 220 397 x 145 x 220 369 x 190 x 318 442 x 190 x 318
Net Weight (kgs) 4.1 6.8 7.4 12 16
ENVIRONMENT
Humidity 20-90 % RH @ 0- 40°C (Non-condensing) 0-95% RH @ 0-50°C (non-condensing) 0-95% RH @ 0-40°C (non-condensing)
Noise Level Less than 50dBA @ 1 Meter Less than 55dBA @ 1 Meter Less than 58dBA @ 1 Meter
MANAGEMENT
Smart RS-232/USB Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux, Unix, and MAC
Optional SNMP Power management from SNMP manager and web browser